Low Smoke No Halogen Flame Retardant Fire Resistant Cable
Http://www.ahzdh.com Time: 11/10/10 10:29
The product is used for controlling and supervising return circuit or power system with requirement of rated voltage 600/1000V or lower, low smoke and no halogen,
Executive Standard:
Use enterprise standard or refer to GB9330-88, GB/T12706-2002 standard.
Working condition
- Long-term working temperature of cable is 90℃
- Cable insulation temperature is no less than 0℃. Recommended bending radius is as following:
No halogen flame retardant control cable:
- Bending radius is no less than 12 times that of cable outer diameter for cable with structure of armoring and copper tape shielding
- Bending radius is no less than 6 times that of cable outer diameter for cable with other structure
No halogen flame retardant power cable:
- Bending radius is no less than 20 times that of cable outer diameter for cable with single core
- Bending radius is no less than 15 times that of cable outer diameter for cable with multi cores
Cable Type & Name
Type |
Name |
|
Copper core |
Aluminum core |
|
WDZ-YJY |
WDZ-YJLY |
Copper core (aluminum core) XLPE insulation low smoke no halogen flame retardant power cable |
WDZ-YJY23 |
WDZ-YJLY23 |
Copper core (aluminum core) XLPE insulation steel tape armoring low smoke no halogen flame retardant power cable |
WDZ-YJY33 |
WDZ-YJLY33 |
Copper core (aluminum core) XLPE insulation thin steel wire armoring low smoke no halogen flame retardant power cable |
EDZN-YJY |
/ |
Copper core XLPE insulation low smoke no halogen flame retardant fire resistant power cable |
WDZN-YJY23 |
/ |
Copper core XLPE insulation steel tape armoring low smoke no halogen flame retardant fire resistant power cable |
WDZN-YJY33 |
/ |
Copper core XLPE insulation thin steel wire armoring low smoke no halogen flame retardant fire resistant power cable |
Type |
Name |
WDZ-KYJY |
Copper core XLPE insulation low smoke no halogen flame retardant control cable |
WDZ-KYJYP |
Copper core XLPE insulation copper wire shielding low smoke no halogen flame retardant control cable |
WDZ-KYJYP2 |
Copper core XLPE insulation copper tape shielding low smoke no halogen flame retardant control cable |
WDZ-KYJYP2-23 |
Copper core XLPE insulation copper tape shielding steel tape armoring low smoke no halogen flame retardant control cable |
WDZ-KYJY33 |
Copper core XLPE insulation thin steel wire armoring low smoke no halogen flame retardant control cable |
WDZN-KYJY |
Copper core XLPE insulation low smoke no halogen flame retardant fire resistant control cable |
WDZN-KYJYP2 |
Copper core XLPE insulation copper tape shielding low smoke no halogen flame retardant fire resistant control cable |
WDZN-KYJYP2-23 |
Copper core XLPE insulation copper tape shielding steel tape armoring low smoke no halogen flame retardant fire resistant control cable |
Main technical parameter:
- Conductor DC resistance is in accordance with GB/T3956 standard
- Insulated resistance constant is no less than 3.67MΩ.km at 90℃. Volume resistance ratio is no less than 1012Ω.Cm
- Cable shall endure 3.5kv A.C. voltage test for 5 minutes without puncture
- Performance target of no halogen, low smoke and flame retardant.
Test item |
Unit |
Requirement |
Teat method |
Smoke density test |
% |
60 |
GB/T17651-1998 |
Corrosive test |
µ S/mm |
4.3 |
GB/T17650.2-1998(idtIEC60754) |
Hydrogen halogen gas content |
Mg/g |
≤5 |
GB/T17650.1-1998(idtIEC60754) |
Bundle burning test |
Min |
A B C |
GB/T18380.3-2001(replace for GB12666.5-90) |
Copyright © 2009-2011 Anhui Electric (Group) Shares Co., Ltd.